Loona Construction Calculators
Loona Construction Calculators › Electrical › Amps to Watts Calculator

🔌 Amps to Watts Calculator

How many watts is that current draw? Enter the amps and volts, choose DC, single-phase or three-phase, set the power factor for AC motor-type loads, and get the real power in watts and kilowatts — plus the apparent power in kVA.

How to use the Amps to Watts Calculator

  1. Choose the system: DC, AC single-phase, or AC three-phase.
  2. Enter the current in amps and the voltage — for three-phase, the line-to-line voltage (e.g. 400 V).
  3. For AC, enter the power factor: 1.0 for heaters and other resistive loads, typically 0.75–0.9 for motors. DC ignores the power factor. Press Calculate.
Example: 10 A at 230 V single-phase with a power factor of 0.8: P = 230 × 10 × 0.8 = 1,840 W.

Frequently Asked Questions

Why do I need the voltage to turn amps into watts?

Amps measure flow, watts measure power — and power is flow × pressure (voltage). 10 A at 12 V is only 120 W, while 10 A at 230 V is 2,300 W. There is no single amps-to-watts conversion without a voltage.

What power factor should I use?

1.0 for resistive loads (heaters, kettles, incandescent lamps) and for DC. Motors, compressors and fluorescent or LED drivers run lower — 0.75–0.9 is typical for motors; the load's nameplate or datasheet gives its actual figure.

What is the difference between watts and VA / kVA?

Watts are real power — the part that does work and appears on your bill. Volt-amps are apparent power — watts divided by the power factor — and are what cables, breakers, transformers and generators must be sized for.

Related Calculators

🔁

Watts to Amps Calculator

Electrical

🔺

Three-Phase Power Calculator

Electrical

🎚️

Power Factor Calculator

Electrical

⚡

Ohm's Law Calculator

Electrical

How it works — the formula

DC: P = V × I
AC single-phase: P = V × I × PF
AC three-phase: P = √3 × VL-L × I × PF
Apparent power: S = V × I (single-phase / DC) or √3 × VL-L × I (three-phase), shown in kVA.

Amps alone do not tell you power — the same 10 A is 120 W on a 12 V DC circuit, 2,300 W on a 230 V resistive circuit, and over 5.5 kW on a 400 V three-phase supply. That is why the voltage, the system type and (for AC) the power factor all matter.

Worked example

Single-phase, I = 10 A, V = 230 V, PF = 0.8: P = 230 × 10 × 0.8 = 1,840 W (1.84 kW). The apparent power is 230 × 10 = 2,300 VA = 2.30 kVA — the difference between the two is the power factor at work.

Frequently asked questions

How do I do this for a three-phase load?

Use the three-phase option with the line-to-line voltage (400 V in most of Europe, 480 V / 208 V in North America) and the line current. The √3 factor in the formula accounts for the three phases sharing the load.

Can I get kilowatts directly?

Yes — the result shows watts and kilowatts together (watts ÷ 1,000). For billing and comparing with motor or generator ratings, kW is usually the handier unit.

Is 1 amp always 230 watts in Europe?

Only on a 230 V single-phase circuit with a power factor of 1. With a motor at PF 0.8 the same amp is 184 W of real power — a common source of undersized estimates.

Embed this calculator on your website — free

Add this calculator to your own website or blog — it is completely free, needs no sign-up, and always shows the latest version. Copy the code below and paste it into your page where you want the calculator to appear. Keeping the small “Powered by Loona Automation” credit line under the embed helps keep this tool free — but you are free to style or remove it; the tool works either way.