Enter a load's real power in kW and its apparent power in kVA and get the power factor, the reactive power in kvar and the phase angle — and, if you set a target, the size of correction capacitor (in kvar) that would get you there.
1.0 is perfect and typical of resistive loads. 0.95 or better is the usual target for industrial installations; many utilities start penalising below 0.9 or 0.95 on commercial tariffs. Small motors running lightly loaded can fall to 0.6–0.7.
The supply, cables and transformer carry current in proportion to kVA, not kW. At PF 0.8 a 100 kW load needs the infrastructure of a 125 kVA load — more losses, bigger equipment, and often an explicit low-PF charge on commercial bills.
Single-phase: kVA = V × A ÷ 1,000. Three-phase: kVA = √3 × V(line-line) × A ÷ 1,000. The kVA to Amps Calculator does the same maths in reverse.
Power factor: PF = kW ÷ kVA = cos φ
Reactive power: Q = √(kVA² − kW²)
Correction capacitor: Qc = kW × (tan φ1 − tan φ2), where φ1 is the present angle and φ2 the target angle.
The three powers form a right-angled triangle: kW along the base (useful work), kvar vertical (magnetising energy that motors and transformers cycle back to the supply), and kVA as the hypotenuse (what the supply actually carries). The power factor is the cosine of the angle between kW and kVA — 1.0 is a flat triangle with no waste, and every step below 1 means more current for the same work.
Yes — inductive loads (motors, transformers, fluorescent ballasts) consume lagging reactive power, and capacitors supply leading reactive power. Correctly sized, automatically switched capacitor banks are standard industrial equipment. They must be specified properly: over-correction can cause its own problems, and harmonics may need detuned reactors.
Bills for homes are almost everywhere charged on kWh (real energy), so a poor PF costs you little directly — though the extra current still heats your wiring. It matters most for businesses on kVA or demand tariffs.
No. Efficiency is useful output ÷ electrical input (a motor's shaft kW ÷ its electrical kW). Power factor is real ÷ apparent power at the input. A motor can be 90% efficient and still have a 0.8 power factor.
Add this calculator to your own website or blog — it is completely free, needs no sign-up, and always shows the latest version. Copy the code below and paste it into your page where you want the calculator to appear. Keeping the small “Powered by Loona Automation” credit line under the embed helps keep this tool free — but you are free to style or remove it; the tool works either way.