Generators, transformers and UPS units are rated in kVA — but breakers and cables work in amps. Convert either way: kVA + voltage gives the full-load current, or amps + voltage gives the kVA a load needs.
Because their limit is current and voltage — the heating in their windings depends on amps, not on how much of that current does useful work. A 50 kVA generator can supply 50 kW to a resistive load (PF 1) but only 40 kW to a load at PF 0.8, at the same 72 A on a 400 V three-phase output.
Multiply by the power factor: kW = kVA × PF. At the common generator rating assumption of PF 0.8, 50 kVA = 40 kW. The Power Factor Calculator works through the full triangle.
The line-to-line voltage — the one in the system's name: 400 V for a 400/230 V system, 480 V, 208 V or 600 V in North America. Do not use the 230 V line-to-neutral figure in the three-phase formula.
Single-phase: I = kVA × 1,000 ÷ V · kVA = V × I ÷ 1,000
Three-phase: I = kVA × 1,000 ÷ (√3 × VL-L) · kVA = √3 × VL-L × I ÷ 1,000
kVA (apparent power) is voltage × current with no power-factor adjustment — that is why generators and transformers are rated in it: they must supply the current whatever the load's power factor. Real power in kW = kVA × PF.
At 400 V three-phase, 1 kVA = 1.44 A. At 230 V single-phase, 1 kVA = 4.35 A. At 120 V single-phase, 8.33 A. Always state the voltage with any kVA-to-amps figure.
It gives the running current. Motors draw 6–8× their running current while starting, so generator sizing for motor loads needs the starting kVA checked too — a common rule is that the generator's kVA should comfortably exceed the motor's starting demand or a soft starter should be fitted.
Just scale: 1 kVA = 1,000 VA. Small UPS units are often rated in VA (e.g. 1,500 VA = 1.5 kVA); the formulas here work if you enter VA ÷ 1,000 as kVA.
Add this calculator to your own website or blog — it is completely free, needs no sign-up, and always shows the latest version. Copy the code below and paste it into your page where you want the calculator to appear. Keeping the small “Powered by Loona Automation” credit line under the embed helps keep this tool free — but you are free to style or remove it; the tool works either way.