Convert American Wire Gauge to the numbers the rest of the world uses: diameter in mm and inches, cross-section in mm², and resistance per kilometer for copper and aluminum — or go the other way, from mm² or diameter to the nearest AWG.
AWG comes from the number of drawing dies a wire was pulled through in the 19th century — higher number, thinner wire. Its sizes (…3.31, 5.26, 8.37 mm²…) simply land between the metric preferred sizes (…2.5, 4, 6, 10 mm²…), so every conversion is a nearest match, not an equality.
Pick the AWG whose area is at or above your requirement. Example: needing 2.5 mm², 14 AWG gives only 2.08 mm² (not enough) — 13 AWG at 2.62 mm² is the first size that covers it. This converter shows the nearest by area; for a minimum requirement, step one gauge thicker if the nearest is below your figure.
No — deliberately. Ampacity depends on the insulation type, installation method, grouping and ambient temperature, and is defined by your local wiring code's tables, not by the gauge alone. This page converts sizes and resistance only; use the Wire Size and Voltage Drop calculators for drop, and your code (or an electrician) for ratings.
AWG is a geometric series: each step changes the diameter by a fixed ratio (about ×1.123), so area roughly doubles every 3 gauges and diameter doubles every 6. The diameter and area figures here are the standard nominal values for each gauge (the series standardized in ASTM B 258, rounded for display).
Resistance per km = ρ × 1,000 ÷ Area (mm²), computed with ρ = 0.0168 Ω·mm²/m for copper and 0.0265 Ω·mm²/m for aluminum at 20 °C — the resistivity constants used consistently across this site's electrical calculators. Real conductors vary a little with stranding, temper and temperature (copper's resistance rises about 0.39% per °C).
Sources differ in the resistivity they assume (1.68 vs 1.72 ×10⁻⁸ Ω·m for copper are both common), in temperature (20 °C vs 25 °C), and in whether the conductor is solid or stranded. The differences are a few percent; this page states its constants so you can reproduce every figure.
Strip the insulation and measure the conductor diameter with calipers or a micrometer (for stranded wire, measure one strand and multiply its area by the strand count, or use a printed AWG gauge plate). Then use diameter mode here for the nearest gauge.
Below 1 AWG the series continues as 0 (written 1/0), 00 (2/0), 000 (3/0) and 0000 (4/0) — progressively thicker conductors used for service entrances, battery cables and heavy feeders.
Add this calculator to your own website or blog — it is completely free, needs no sign-up, and always shows the latest version. Copy the code below and paste it into your page where you want the calculator to appear. Keeping the small “Powered by Loona Automation” credit line under the embed helps keep this tool free — but you are free to style or remove it; the tool works either way.