Tell this calculator the current, the one-way run length, the supply voltage and the voltage drop you can accept, and it works out the minimum cable cross-section — then rounds up to the nearest standard size in mm² with its AWG equivalent.
Cable is manufactured in standard cross-sections. Rounding down to the size below the calculated minimum would exceed your drop limit, so the calculator always rounds up — and the result box shows the (lower) drop the standard size actually gives.
No — and that matters. This tool solves the voltage-drop half of cable sizing only. Ampacity (safe current-carrying capacity) depends on how the cable is installed — in free air, conduit, insulation or underground — and on temperature and grouping. Check the size against your local code's ampacity tables, or ask an electrician, and use the larger of the two sizes.
Aluminum's resistivity is about 1.58× copper's, so for the same drop limit it needs roughly 58% more cross-section — in practice one or two standard steps up. Aluminum also needs suitable terminations; follow local code for its use.
Allowed drop (V) = Supply voltage × Allowed % ÷ 100
Single-phase: A = 2 × I × ρ × L ÷ Allowed drop
Three-phase: A = √3 × I × ρ × L ÷ Allowed drop
with ρ = 0.0168 Ω·mm²/m for copper (1.68 × 10−8 Ω·m) and 0.0265 Ω·mm²/m for aluminum (2.65 × 10−8 Ω·m), L the one-way length in meters and A the cross-section in mm². The raw minimum is then rounded up to the next standard size (1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240 mm²), and the AWG figure is the nearest common American gauge to that standard size — an approximation, since the two systems' steps do not line up exactly.
No. AWG sizes (…3.31 mm² for 12 AWG, 5.26 mm² for 10 AWG…) do not coincide with metric standard sizes, so the figure shown is the nearest common gauge. If you are buying by AWG and the equivalent sits between gauges, choose the thicker (lower-numbered) gauge.
Common guidance (IEC 60364-5-52 informative annex and national rules based on it) is about 3% for lighting and 5% for other uses, from the origin of the installation. If part of that budget is already used by an upstream run, allow only what remains for this run.
Very long or heavy runs are normally solved with parallel cables, a higher supply voltage, or moving the supply closer to the load. That is specialist design territory — bring in a qualified electrician or electrical engineer.
Add this calculator to your own website or blog — it is completely free, needs no sign-up, and always shows the latest version. Copy the code below and paste it into your page where you want the calculator to appear. Keeping the small “Powered by Loona Automation” credit line under the embed helps keep this tool free — but you are free to style or remove it; the tool works either way.