Long cable runs lose voltage along the way. Enter the one-way length, the current, the conductor material and the cable size (mm² or AWG) and get the volts dropped and the percentage drop, checked against the familiar 3% / 5% guidance.

How to use the Voltage Drop Calculator

  1. Measure the one-way distance from the supply to the load — the formula already counts both conductors of a single-phase run, so do not double your measurement.
  2. Enter the current the load actually draws, the supply voltage, the conductor material and whether the supply is single-phase or three-phase.
  3. Pick the cable size in mm², or use the AWG selector if your cable is sold by gauge, then press Calculate.
Example: A 20 m single-phase copper run carrying 16 A in 2.5 mm² cable at 230 V drops 4.30 V — 1.87%, comfortably inside the guide values.

Frequently Asked Questions

Why does voltage drop matter?

Equipment at the end of a long, thin run receives less than the supply voltage: lights dim, motors run hot and can stall, and electronics may misbehave. The energy lost in the cable is also wasted as heat. Keeping drop within a few percent keeps loads working as designed.

What do the 3% and 5% limits mean?

They are widely used guidance values, found in the informative annex of IEC 60364-5-52 and in many national wiring rules derived from it: a total drop of about 3% of nominal voltage for lighting circuits and 5% for other (power) circuits, from the origin of the installation to the load. Your local code is the authority — these figures are context, not a substitute for it.

Why is aluminum's drop higher than copper's?

Aluminum's resistivity (2.65 × 10⁻⁸ Ω·m) is about 1.58× copper's (1.68 × 10⁻⁸ Ω·m), so the same length and size of aluminum cable drops about 58% more volts. Aluminum runs are normally sized one or two steps thicker to compensate.

Related Calculators

🧵

Wire Size Calculator

Electrical

⚡

Ohm's Law Calculator

Electrical

💷

Electricity Cost Calculator

Electrical

☀️

Solar Panel Calculator

Electrical

How it works — the formula

Single-phase: Vdrop = 2 × I × ρ × L ÷ A
Three-phase (balanced): Vdrop = √3 × I × ρ × L ÷ A
% drop = Vdrop ÷ Supply voltage × 100

where I is current (A), L is the one-way length (m), A is the conductor cross-section (mm²), and ρ is the conductor resistivity expressed as 0.0168 Ω·mm²/m for copper (ρ = 1.68 × 10−8 Ω·m) and 0.0265 Ω·mm²/m for aluminum (ρ = 2.65 × 10−8 Ω·m). The factor 2 in the single-phase formula is the go-and-return pair of conductors; √3 is its three-phase equivalent. The 3% and 5% figures come from the informative guidance in IEC 60364-5-52 (and national rules based on it): roughly 3% of the supply voltage for lighting circuits and 5% for other uses, from the origin of the installation to the point of use.

Worked example

Single-phase copper, L = 20 m, I = 16 A, A = 2.5 mm², 230 V supply: Vdrop = 2 × 16 × 0.0168 × 20 ÷ 2.5 = 10.752 ÷ 2.5 = 4.30 V. As a percentage: 4.30 ÷ 230 × 100 = 1.87% — inside both the 3% lighting and 5% power guide values.
Safety note: this calculator is a planning aid using a simplified resistive model. Real installations must also satisfy cable current-carrying capacity, protective-device and earthing requirements under your local wiring code — have the work designed or checked by a qualified electrician.

Frequently asked questions

Do I enter the length there-and-back?

No — enter the one-way distance only. The factor 2 (single-phase) or √3 (three-phase) in the formula already accounts for the full current path.

What about cable reactance and power factor?

For small cables (up to about 16–25 mm²) resistance dominates and this simplified calculation is close. For large cables, long runs and highly inductive loads, reactance and power factor add to the drop; a full IEC-style calculation or an electrician's check is then worthwhile.

My drop is too high — what are my options?

Use a thicker cable (the most effective fix — doubling the cross-section halves the drop), shorten the route, split the load across two circuits, or, where the system allows it, supply the load at a higher voltage (a three-phase supply drops proportionally less at 400 V than a single-phase one at 230 V for the same power).

Embed this calculator on your website — free

Add this calculator to your own website or blog — it is completely free, needs no sign-up, and always shows the latest version. Copy the code below and paste it into your page where you want the calculator to appear. Keeping the small “Powered by Loona Automation” credit line under the embed helps keep this tool free — but you are free to style or remove it; the tool works either way.