Estimate a motor's full-load current from its rated power — in kW or horsepower — its voltage, phase, efficiency and power factor. Useful for early planning and sanity checks; the nameplate and code tables remain the authority, as the notes below explain.
Efficiency and power factor vary with the individual motor's design and with its load — a motor at half load draws less current but at a worse power factor. Two motors with the same kW rating from different makers can differ by 10% in full-load amps, which is why standards insist on the nameplate figure.
Choose the hp option — the calculator converts at 1 hp = 0.7457 kW. (For converting power units on their own, Loona Calculators has dedicated horsepower ↔ kilowatt converters; here the conversion is just the first step of the current estimate.)
Modern three-phase motors: efficiency roughly 80% for small motors rising to 93–95% for large premium-efficiency ones; full-load PF typically 0.8–0.87 for small motors and 0.85–0.92 for large. The nameplate or datasheet beats any assumption.
Electrical input power = Shaft power ÷ Efficiency
Single-phase: I = Input W ÷ (V × PF)
Three-phase: I = Input W ÷ (√3 × VL-L × PF)
Horsepower: kW = hp × 0.7457
The step most quick estimates miss is the first one: a motor's advertised kW or hp is the mechanical power at its shaft. The electrical side must supply that plus the motor's losses, so the input is the shaft power divided by the efficiency — a 7.5 kW motor at 90% efficiency actually takes 8.33 kW from the supply before the power factor is even considered.
Direct-on-line (DOL) starting typically draws 6–8× full-load current for a few seconds — the reason lights dip and why breakers for motor circuits use motor-rated trip curves. Star-delta starting cuts it to about a third; soft starters and VFDs can limit it to 1–1.5×.
Only as a first estimate. Cable and protection for motors follow specific code rules (in the US, NEC Article 430 uses standardised full-load current tables rather than the nameplate for conductor sizing, and allows higher breaker ratings to ride through starting). A qualified electrician applies those rules to the actual nameplate.
On the motor side the VFD supplies whatever the motor needs; on the supply side the drive draws current with its own characteristics and harmonics. Size the supply from the drive maker's input-current rating, not from this estimate.
Add this calculator to your own website or blog — it is completely free, needs no sign-up, and always shows the latest version. Copy the code below and paste it into your page where you want the calculator to appear. Keeping the small “Powered by Loona Automation” credit line under the embed helps keep this tool free — but you are free to style or remove it; the tool works either way.