🔁 Watts to Amps Calculator

You know the watts — a heater's rating, a motor's plate — now find the amps it will draw. Choose DC, single-phase or three-phase, enter the voltage and power factor, and get the current: the number you need before choosing a breaker, fuse or cable.

How to use the Watts to Amps Calculator

  1. Choose DC, AC single-phase or AC three-phase.
  2. Enter the load's power in watts (its rating plate, or watts = kW × 1,000) and the supply voltage.
  3. Set the power factor for AC loads — 1.0 for heaters, about 0.8 for a typical motor — then press Calculate.
Example: A 3,000 W load on 230 V single-phase at PF 0.8 draws 3,000 ÷ (230 × 0.8) = 16.30 A — so a 16 A breaker is not enough; the next size up is needed.

Frequently Asked Questions

Why does the power factor change the amps?

Only part of the current drawn by an inductive load does useful work. At a power factor of 0.8, the supply must deliver 1 ÷ 0.8 = 1.25× the current that the watts alone suggest, so cables and breakers see the higher figure.

Which breaker size do I need for the result?

The breaker must be rated at or above the load current, and many codes require 125% sizing for continuous loads (running 3+ hours). The calculator shows the true load current; applying your local code's margins and choosing the breaker and cable is the next step — see the Wire Size Calculator.

How many amps is 1,000 W?

It depends on voltage and power factor: at 230 V and PF 1 it is 4.35 A; at 230 V and PF 0.8, 5.43 A; at 120 V and PF 1, 8.33 A; on a 12 V DC circuit, 83.3 A — which is why low-voltage systems need such thick cables.

Related Calculators

🔌

Amps to Watts Calculator

Electrical

🌀

Motor Current Calculator

Electrical

🧵

Wire Size Calculator

Electrical

⚡

Ohm's Law Calculator

Electrical

How it works — the formula

DC: I = P ÷ V
AC single-phase: I = P ÷ (V × PF)
AC three-phase: I = P ÷ (√3 × VL-L × PF)

These are the power-law formulas rearranged. Notice what the power factor does: at PF 0.8 the same watts need 25% more current than at PF 1 — which is why motor loads surprise people who divide watts by volts and stop there.

Worked example

P = 3,000 W, V = 230 V, PF = 0.8, single-phase: I = 3,000 ÷ (230 × 0.8) = 3,000 ÷ 184 = 16.30 A. The same load as a pure resistance (PF 1) would draw 3,000 ÷ 230 = 13.04 A — the power factor alone added over 3 A.

Frequently asked questions

Does this work for a motor's rated kW?

A motor's plate kW is usually its shaft (output) power. The electrical input is higher because of motor losses, so use the Motor Current Calculator, which adds efficiency to the calculation, for a better full-load current estimate — and always prefer the nameplate FLA when you have it.

What about three-phase — which voltage do I enter?

The line-to-line voltage: 400 V on a typical European 400/230 V system, 480 V or 208 V in North America. The formula's √3 handles the rest.

Can I convert amps back to watts?

Yes — that is the companion Amps to Watts Calculator, linked below; the two are exact inverses when the same voltage and power factor are used.

Embed this calculator on your website — free

Add this calculator to your own website or blog — it is completely free, needs no sign-up, and always shows the latest version. Copy the code below and paste it into your page where you want the calculator to appear. Keeping the small “Powered by Loona Automation” credit line under the embed helps keep this tool free — but you are free to style or remove it; the tool works either way.