Long cable runs lose voltage along the way. Enter the one-way length, the current, the conductor material and the cable size (mm² or AWG) and get the volts dropped and the percentage drop, checked against the familiar 3% / 5% guidance.
Equipment at the end of a long, thin run receives less than the supply voltage: lights dim, motors run hot and can stall, and electronics may misbehave. The energy lost in the cable is also wasted as heat. Keeping drop within a few percent keeps loads working as designed.
They are widely used guidance values, found in the informative annex of IEC 60364-5-52 and in many national wiring rules derived from it: a total drop of about 3% of nominal voltage for lighting circuits and 5% for other (power) circuits, from the origin of the installation to the load. Your local code is the authority — these figures are context, not a substitute for it.
Aluminium's resistivity (2.65 × 10⁻⁸ Ω·m) is about 1.58× copper's (1.68 × 10⁻⁸ Ω·m), so the same length and size of aluminium cable drops about 58% more volts. Aluminium runs are normally sized one or two steps thicker to compensate.
Single-phase: Vdrop = 2 × I × ρ × L ÷ A
Three-phase (balanced): Vdrop = √3 × I × ρ × L ÷ A
% drop = Vdrop ÷ Supply voltage × 100
where I is current (A), L is the one-way length (m), A is the conductor cross-section (mm²), and ρ is the conductor resistivity expressed as 0.0168 Ω·mm²/m for copper (ρ = 1.68 × 10−8 Ω·m) and 0.0265 Ω·mm²/m for aluminium (ρ = 2.65 × 10−8 Ω·m). The factor 2 in the single-phase formula is the go-and-return pair of conductors; √3 is its three-phase equivalent. The 3% and 5% figures come from the informative guidance in IEC 60364-5-52 (and national rules based on it): roughly 3% of the supply voltage for lighting circuits and 5% for other uses, from the origin of the installation to the point of use.
No — enter the one-way distance only. The factor 2 (single-phase) or √3 (three-phase) in the formula already accounts for the full current path.
For small cables (up to about 16–25 mm²) resistance dominates and this simplified calculation is close. For large cables, long runs and highly inductive loads, reactance and power factor add to the drop; a full IEC-style calculation or an electrician's check is then worthwhile.
Use a thicker cable (the most effective fix — doubling the cross-section halves the drop), shorten the route, split the load across two circuits, or, where the system allows it, supply the load at a higher voltage (a three-phase supply drops proportionally less at 400 V than a single-phase one at 230 V for the same power).
Add this calculator to your own website or blog — it is completely free, needs no sign-up, and always shows the latest version. Copy the code below and paste it into your page where you want the calculator to appear. Keeping the small “Powered by Loona Automation” credit line under the embed helps keep this tool free — but you are free to style or remove it; the tool works either way.